Products Description
Product Features
After normal transportation, this series of transformers can be installed with relevant components, undergo acceptance tests, and be put into operation after passing the tests without core lifting inspection.
Product Overview
The S11-M series fully sealed oil-immersed power transformers developed and produced by our company have the advantages of low loss, low noise and high efficiency, which can achieve good energy-saving effects and reduce pollution.
Compared with ordinary oil-immersed transformers, the fully sealed transformer cancels the oil conservator. The change of oil volume is automatically adjusted and compensated by the elasticity of the corrugated sheets of the corrugated oil tank. The transformer is isolated from air, which prevents and slows down oil deterioration and insulation aging, enhances operational reliability, and requires no maintenance during normal operation.
Main Performance Parameters of S11 Type 10KV Double-Winding Series
| Model | Rated Capacity (kVA) | Connection Group Symbol | Voltage Combination (kV) | No-load Loss (W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance (%) | ||
|---|---|---|---|---|---|---|---|---|---|
| High Voltage | Tap Voltage | Low Voltage | |||||||
| S11-M-30 | 30 | Yyn0 or Dyn11 | 6, 6.3, 10.5, 11 | ±5% or ±2×2.5% | 0.4 | 100 | 630/600 | 1.5 | 4.0 |
| S11-M-50 | 50 | 130 | 910/870 | 1.3 | 4.0 | ||||
| S11-M-63 | 63 | 150 | 1090/1040 | 1.2 | 4.0 | ||||
| S11-M-80 | 80 | 180 | 1310/1250 | 1.2 | 4.0 | ||||
| S11-M-100 | 100 | 200 | 1580/1500 | 1.1 | 4.0 | ||||
| S11-M-125 | 125 | 240 | 1890/1800 | 1.1 | 4.0 | ||||
| S11-M-160 | 160 | 280 | 2310/2200 | 1.0 | 4.0 | ||||
| S11-M-200 | 200 | 340 | 2730/2600 | 1.0 | 4.0 | ||||
| S11-M-250 | 250 | 400 | 3200/3050 | 0.9 | 4.0 | ||||
| S11-M-315 | 315 | 480 | 3820/3650 | 0.9 | 4.0 | ||||
| S11-M-400 | 400 | 570 | 4520/4300 | 0.8 | 4.0 | ||||
| S11-M-500 | 500 | 680 | 5410/5150 | 0.8 | 4.0 | ||||
| S11-M-630 | 630 | 810 | 6200 | 0.6 | 4.5 | ||||
| S11-M-800 | 800 | 980 | 7500 | 0.6 | 4.5 | ||||
| S11-M-1000 | 1000 | 1150 | 10300 | 0.6 | 4.5 | ||||
| S11-M-1250 | 1250 | 1360 | 12000 | 0.5 | 4.5 | ||||
| S11-M-1600 | 1600 | 1640 | 14500 | 0.5 | 4.5 | ||||
| S11-M-2000 | 2000 | 1940 | 18300 | 0.4 | 5.0 | ||||
| S11-M-2500 | 2500 | 2290 | 21200 | 0.4 | 5.0 |
Main Performance Parameters of S11 Type 20KV Double-Winding Series
| Model | Rated Capacity (kVA) | Connection Group Symbol | Voltage Combination (kV) | No-load Loss (W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance (%) | ||
|---|---|---|---|---|---|---|---|---|---|
| High Voltage | Tap Voltage | Low Voltage | |||||||
| S11-M-30 | 30 | Dyn11 | 20 | ±5% | 0.4 | 90 | 600 | 1.5 | 5.5 |
| S11-M-50 | 50 | ±5% | 0.4 | 130 | 960 | 1.3 | 5.5 | ||
| S11-M-63 | 63 | ±5% | 0.4 | 150 | 1145 | 1.2 | 5.5 | ||
| S11-M-80 | 80 | ±5% | 0.4 | 180 | 1370 | 1.2 | 5.5 | ||
| S11-M-100 | 100 | ±5% | 0.4 | 200 | 1650 | 1.1 | 5.5 | ||
| S11-M-125 | 125 | ±5% | 0.4 | 240 | 1980 | 1.1 | 5.5 | ||
| S11-M-160 | 160 | ±5% | 0.4 | 280 | 2420 | 1.0 | 5.5 | ||
| S11-M-200 | 200 | ±5% | 0.4 | 340 | 2860 | 1.0 | 5.5 | ||
| S11-M-250 | 250 | ±5% | 0.4 | 400 | 3350 | 0.9 | 5.5 | ||
| S11-M-315 | 315 | ±5% or ±2×2.5% | 0.4 | 480 | 4010 | 0.9 | 5.5 | ||
| S11-M-400 | 400 | ±5% or ±2×2.5% | 0.4 | 570 | 4730 | 0.8 | 5.5 | ||
| S11-M-500 | 500 | ±5% or ±2×2.5% | 0.4 | 680 | 5660 | 0.8 | 5.5 | ||
| S11-M-630 | 630 | ±5% or ±2×2.5% | 0.4 | 810 | 6820 | 0.6 | 6.0 | ||
| S11-M-800 | 800 | ±5% or ±2×2.5% | 0.4 | 980 | 8250 | 0.6 | 6.0 | ||
| S11-M-1000 | 1000 | ±5% or ±2×2.5% | 0.4 | 1150 | 11330 | 0.6 | 6.0 | ||
| S11-M-1250 | 1250 | ±5% or ±2×2.5% | 0.4 | 1360 | 13200 | 0.5 | 6.0 | ||
| S11-M-1600 | 1600 | ±5% or ±2×2.5% | 0.4 | 1640 | 15950 | 0.5 | 6.0 |